Whole-House Fresh Air Supply

A whole-house mechanical fresh-air supply system is provided.

Spec

A whole-house mechanical fresh-air supply system is provided.

Applies uniformly from Silver upward.

Scope

Continuous or intermittent mechanical ventilation that supplies outdoor air to the dwelling — separate from spot ventilation (bath fans, kitchen hood).

Requirements

  1. 01.

    Install a whole-house ventilation system meeting ASHRAE 62.2-2022 airflow minimums (typically 30-90 CFM for a 1500-3000 sf home, depending on bedrooms).

  2. 02.

    Acceptable system types: dedicated supply fan, exhaust-only with passive inlets, or balanced (supply + exhaust with optional heat recovery — required at Gold).

  3. 03.

    Run-time controls must ensure the design CFM is delivered as an average over each 4-hour period.

Documentation

Evidence the inspector / Institute will need.

  1. 01.

    ASHRAE 62.2 ventilation calculation worksheet showing required CFM for the dwelling.

  2. 02.

    Ventilation system spec sheet + photo of installed fan / controls.

  3. 03.

    Flow test confirming delivered CFM at the grille(s).

Guidance

Why tight houses need this

Modern construction is tight enough that natural infiltration alone no longer dilutes indoor pollutants to safe levels — VOCs from finishes, CO2 from occupants, moisture from cooking/showering, and (for the unlucky) radon all accumulate. The whole-house fan is the air-quality equivalent of a circulating pump in a plumbing system.