Balanced Fresh-Air System

A balanced (supply + exhaust) fresh-air system is installed and tested.

Spec

A balanced (supply + exhaust) fresh-air system is installed and tested.

Applies uniformly from Gold upward.

Scope

Mechanical ventilation system delivering balanced supply and exhaust airflow — HRV (heat recovery ventilator) or ERV (energy recovery ventilator).

Requirements

  1. 01.

    Install a dedicated HRV or ERV sized to ASHRAE 62.2-2022 ventilation rates for the dwelling.

  2. 02.

    Commission with a balance test: measured supply CFM and exhaust CFM must be within 10% of each other.

  3. 03.

    Supply ducting must distribute fresh air to bedrooms and main living areas; exhaust ducting must pull from kitchen, bathrooms, and laundry.

Documentation

Evidence the inspector / Institute will need.

  1. 01.

    HRV/ERV spec sheet showing sensible recovery efficiency (≥ 60% for cold climates, ≥ 70% for ENERGY STAR).

  2. 02.

    Commissioning test report showing measured supply CFM, exhaust CFM, and the balance percentage.

  3. 03.

    Marked floor plan showing supply and exhaust grille locations.

Guidance

HRV vs ERV — which to pick

HRV recovers sensible heat only (temperature). ERV recovers both sensible heat and latent (humidity). Use ERV in hot-humid climates (Zones 2-3) to keep summer humidity out, and in cold-dry climates (Zones 6-7) to keep winter humidity in. HRV is acceptable in mixed climates (Zones 4-5) where humidity transfer is less critical.