Carbon Monoxide Detectors

Hardwired CO detectors installed on every floor and near any fireplace.

Spec

Hardwired CO detectors installed on every floor and near any fireplace.

Applies uniformly from Certified upward.

Scope

Carbon-monoxide detection throughout the dwelling.

Requirements

  1. 01.

    Install UL-certified CO detectors on every floor of the dwelling.

  2. 02.

    Place a CO detector within 10 feet of every bedroom door.

  3. 03.

    Place a CO detector within 10 feet of every fireplace and combustion appliance.

  4. 04.

    Detectors must be hardwired with battery backup (not battery-only).

Documentation

Evidence the inspector / Institute will need.

  1. 01.

    Floor-plan markup showing CO-detector locations.

  2. 02.

    Photos of installed detectors (showing the UL listing label).

Guidance

Combination vs dedicated detectors

Combination smoke + CO detectors satisfy this requirement. Standalone CO detectors are also fine. The key is coverage per the placement rules above. Replace all detectors every 10 years (per UL 2034 sensor lifespan) — most current models have a built-in end-of-life chirp.

Note

Low-level CO detectors (sensitive to 10-30 ppm) provide a much earlier warning than standard UL-listed units, which only alarm at 70+ ppm sustained for over an hour. Not required by this standard, but recommended for households with children, pregnant occupants, or anyone with heart/respiratory issues.