Whole-Home Humidity Control

Whole-home dehumidification / humidification provided where appropriate by climate (target 40–50°F dewpoint).

Spec

Whole-home dehumidification / humidification provided where appropriate by climate (target 40–50°F dewpoint).

Applies uniformly from Platinum upward.

Scope

Whole-home humidity management — dehumidification in cooling season, humidification in heating season, as appropriate to climate.

Requirements

  1. 01.

    Install a whole-home dehumidifier (typically integrated with the HVAC return) sized for the dwelling.

  2. 02.

    Target dewpoint range: 40-55°F (corresponds to ~30-50% RH at typical indoor temperatures).

  3. 03.

    In cold-dry climates (Zones 6-8), add a whole-home humidifier to prevent winter RH dropping below 30%.

  4. 04.

    Controls must be tied to the IAQ sensor required at Gold.

Documentation

Evidence the inspector / Institute will need.

  1. 01.

    Dehumidifier (and humidifier where applicable) spec sheets showing pint/day capacity and integration.

  2. 02.

    Photo of installed unit + control interface.

  3. 03.

    Initial commissioning record showing RH/dewpoint readings in main living area.

Guidance

Why dehumidification is separate from AC

In hot-humid climates, a properly-sized AC removes humidity as a side effect of cooling — but only when it's running. During mild "shoulder" periods (May, October), the AC doesn't run enough to control humidity, and indoor RH can climb to 65-75%. A dedicated dehumidifier handles the gap.

Note

Mold growth becomes likely above 60% sustained RH on cool surfaces. Most building scientists recommend keeping RH between 30% (winter floor) and 50% (summer ceiling). Below 30% causes static, dry skin, increased respiratory infection; above 60% causes mold + dust mite growth.